BK Precision 9130 Triple Output Power Supply 17-Apr-2015 K. Goetze To run the BK9130 with EPICS (RS232): ==================================== RS232 Comms: Baud: 9600 - The device can be set to 4800, 9600, 19.2K, or 38.4K. I tested at 9600. Parity: No - The device can be set to Odd, Even, or No Parity. Stop bits: 1 Data bits: 8 Handshaking: No inputEos: LF outputEos: LF Cable: db9 DTE BK9130 db9* ------- ---------- 2 2 3 3 5 5 * Notes Re. Serial connection: 1.) This device's db9 connector is NOT RS232. It is a TTL interface. An adapter needs to be purchased from BK Precision that translates the TTL to RS232. This adapter is port-powered. This means that, for a low-power UART like the IP-Octal, +12VDC needs to be connected on the RS232 side of the adapter to db9 pins 4 (+), and 5 (-). Loading the database, for example: # BK Precision 9130 Power Supply dbLoadRecords("$(IP)/ipApp/Db/BK9130.db","P=xyz:,PS=1,PORT=serial2") StreamDevice: BK9130.proto must be in "STREAM_PROTOCOL_PATH" Autosave: BK9130_settings.req (can be used with "configMenu" to save instrument setups) The arguments for the medm display are simply: P=xyz:, PS=1