vs Record Reference Table of contents The vs (vacuum sensor) record type supports vacuum gauge controllers. It handles ion gauge pressure readback, convectron gauge pressures, setpoint status and values, ion gauge on/off control, degas control, and alarm checking. The record communicates with hardware through the devVacSen device support driver using ASYN.
Device support types (DTYP): devGP307 (GP307), devGP350 (GP350), devMM200 (Televac MM200), devCC10 (Televac CC10), devMX200 (Televac MX200).
Configuration Field Type Description Access INP INLINK Device specification (ASYN port, address) Config TYPE MENU Controller type Config PREC SHORT Display precision Config (default: 1) ERR SHORT Controller error count Read/Write (default: 5)
Value String Device 0 GP307 Granville-Phillips 307 1 GP350 Granville-Phillips 350 2 MM200 Televac MM200 3 CC10 Televac CC10 4 MX200 Televac MX200
Ion Gauge Control Field Type Description Access IG1S MENU Ion gauge 1 set (command) Read/Write (Off/On) IG1R MENU Ion gauge 1 readback (status) Read-only (Off/On) IG2S MENU Ion gauge 2 set (command) Read/Write (Off/On) IG2R MENU Ion gauge 2 readback (status) Read-only (Off/On) DGSS MENU Degas set (command) Read/Write (Off/On) DGSR MENU Degas readback (status) Read-only (Off/On) FLTR MENU Fault readback Read-only (Off/On)
Pressure Readback Linear Pressure Field Type Description Access VAL DOUBLE Ion gauge pressure Read-only PRES DOUBLE Ion gauge pressure (duplicate) Read-only CGAP DOUBLE Convectron gauge A pressure Read-only CGBP DOUBLE Convectron gauge B pressure Read-only
Log10 Pressure Field Type Description Access LPRS DOUBLE Ion gauge log10 pressure Read-only LCAP DOUBLE Convectron A log10 pressure Read-only LCBP DOUBLE Convectron B log10 pressure Read-only
Setpoint Status Field Type Description Access SP1 MENU Setpoint 1 status Read-only (Off/On) SP2 MENU Setpoint 2 status Read-only (Off/On) SP3 MENU Setpoint 3 status Read-only (Off/On) SP4 MENU Setpoint 4 status Read-only (Off/On) SP5 MENU Setpoint 5 status Read-only (Off/On) SP6 MENU Setpoint 6 status Read-only (Off/On)
Setpoint Values Field Type Description Access SP1S DOUBLE Setpoint 1 value set Read/Write SP1R DOUBLE Setpoint 1 readback Read-only SP2S DOUBLE Setpoint 2 value set Read/Write SP2R DOUBLE Setpoint 2 readback Read-only SP3S DOUBLE Setpoint 3 value set Read/Write SP3R DOUBLE Setpoint 3 readback Read-only SP4S DOUBLE Setpoint 4 value set Read/Write SP4R DOUBLE Setpoint 4 readback Read-only
Alarm Fields The record checks the VAL field (ion gauge pressure) against these limits.
Field Type Description Default HIHI FLOAT IG pressure hihi alarm limit 1e-06 HIGH FLOAT IG pressure high alarm limit 1e-07 LOW FLOAT IG pressure low alarm limit 2e-12 LOLO FLOAT IG pressure lolo alarm limit 1e-12 HHSV MENU Hihi alarm severity NO_ALARM HSV MENU High alarm severity NO_ALARM LSV MENU Low alarm severity NO_ALARM LLSV MENU Lolo alarm severity NO_ALARM HYST DOUBLE Alarm deadband 0 LALM DOUBLE Last value alarmed (internal)
Display Range Fields These fields set the display range for GUI screens.
Ion Gauge Field Type Description Default HOPR FLOAT IG pressure display high 0.0001 LOPR FLOAT IG pressure display low 1e-12 HLPR FLOAT IG log10 pressure display high -4 LLPR FLOAT IG log10 pressure display low -12
Convectron Gauge A Field Type Description Default HAPR FLOAT CGA pressure display high 1000 LAPR FLOAT CGA pressure display low 0.0001 HALR FLOAT CGA log10 pressure display high 3 LALR FLOAT CGA log10 pressure display low -4
Convectron Gauge B Field Type Description Default HBPR FLOAT CGB pressure display high 1000 LBPR FLOAT CGB pressure display low 0.0001 HBLR FLOAT CGB log10 pressure display high 3 LBLR FLOAT CGB log10 pressure display low -4
Internal Fields These fields are used internally by the record for change detection. They store previous values and should not be modified directly.
Field Type Description CHGC USHORT Changed control flags PI1S, PI2S MENU Previous ion gauge set commands PDSS MENU Previous degas set command PIG1, PIG2 MENU Previous ion gauge readback PDGS MENU Previous degas readback PFLT MENU Previous fault readback PSP1–PSP6 MENU Previous setpoint status PS1S–PS4S DOUBLE Previous setpoint set values PS1R–PS4R DOUBLE Previous setpoint readbacks PVAL, PPRE DOUBLE Previous gauge pressure PCGA, PCGB DOUBLE Previous convectron pressures PLPE DOUBLE Previous IG log10 pressure PLCA, PLCB DOUBLE Previous convectron log10 pressures