MW100 Support Documentation
This module has support for the Yokogawa MW100 Digital Acquisition Unit. It was written for Linux IOCs, where dynamic memory allocation is not a problem, while others might work as well. It was also written assuming the /M1 math option is present.
This device uses a network interface to communicate, and has a modular design to allow the mixing of DAC, ADC, relay, TTL, and other modules. It is also an industrial device primarily used for monitoring, so its design is not optimized for high performance operation. The system is actually quite complex, as it can: read modbus channels over both serial and the network, perform calculations on the measurements, set alarms, do logging, etc. Some subset of the functionality is supported, and features have been added as needed. However, there is no attempt made to utilize the full capability of the device from EPICS, although the device can be simultaneously controlled by vendor software or the built-in web server, as it supports multiple simultaneous and independent connections.
I assume that the support works for all modules, but this has been tested only with the following: MX110-UNV-M10, MX115-D05-H10, MX120-VAO-M08, and MX125-MKC-M10.
Channel descriptions
The MW100 can handle up to 60 measurement channels, referred to as channels 001-060. The math option adds 300 computation channels (A001-A300), 300 communication input channels (C001-C300), and 60 constant channels (K01-K60).
The module bus can have up to 6 modules on it. The maximum number of I/O channels for the MW100 is 60 (referred to as channels 001-060), with a maximum of 10 channels per modules. Each module has a dedicated slice of the 60 channels, with the first module owning 001-010, the second owning 011-020, etc. The first module is the one closest to the main module.
Setting up the unit
Due to the complexity of the MW100, the configuration of the unit currently needs to be done through its web interface. This includes not only service configuration, but also channel configuration. The way the unit works is that there are modes of operation. Any configuration needs to be done while in the "Settings" mode and computations are stopped, while all data acquisition is done in the "Meaurements" mode and the computations should be started. The mode can be toggled from EPICS or through the native web server. So to do configuration changes, make sure the unit is in Settings mode and do the changes through the web server.
Upon getting the unit, get it on your network, as described in the manual.
Plug your modules into the module bus, realizing that each module location to the left of the main module has an address starting at 1,and increases as you go left.
Operation
Once the unit is configured and running on the network, the EPICS support in this module will work for reading data while in measurement mode, and reading calculations when math is enabled.
The default way the measurements are done is that there are two records that trigger reading all of the values on the device, one for input values (such as ADC and TTL) and another for output values (such as DAC and relay). By default, both records use a time value in their SCAN fields to periodically poll values and put them into a cache, and the record for these values are set to I/O Intr which allow them to be updated by an interrupt call. If a measurement record is decoupled from the master poll rates by setting their SCAN field to a time value, the measurement data associated with a record will be retrieved, with all the associated information (status and alarms) put into the cache, and the new value will be returned; however, the associated status and alarm records for the measurement will return cached values only. This means that to do read an independent channel is to read the measurement value, then forward link to all the associated records to grab the cached values from that read.
The device calculations, communication inputs, and constants are read by the pollers. The calculations (which need to be defined through the web interface) allow the transformation of measurements with the communication input values and predefined constants. The first 60 calculation channels allow for a long calculation (string length of 120 characters), while the last 240 channels allow for short calculations (8 or 10 characters, depending on firmware version).
When an error happpens, the error string is displayed, split into three 40-character string records. The error can be cleared, which also clears it from the units LED display.
Modules
The analog input modules (110 and 112 series) are of the typical voltage/current measuring or the strain gauge measuring types. The first type has many configuration options, such as configured as a thermocouple reader, giving a result through EPICS as a temperature value and units.
I have had no access to integer digital input modules (114 series), but hopefully the support works for them.
The binary digital input modules (115 series) can be used to sense a circuit closure or a voltage level.
The analog output modules (120 series) are only directly controlled by EPICS if they are put into communication mode ("Comm. Input"). If a channel is put into the other mode ("Trans"), it is controlled by other MW100 channels, although the value can still be read by EPICS.
The digital output modules (125 series) act as relays, and are typically used in one of two modes. One is direct control from EPICS ("Comm. Input"), and the other is for it to be controlled by a MW100 alarm ("Alarm").
Driver
The EPICS driver for the MW100 needs to be loaded using the command mw100Init.
mw100Init( instrument handle, IP address)
The instrument handle is a string, provided by the user, that is used by records to refer to this particular MW100. For each MW100 loaded, a different handle needs to be used.
mw100_probe
Included with the module is the source code for mw100_probe utility, that will be built alongside the module. This program will generate automatically a substitutions file auto_mw100.substitutions and an autosave file auto_mw100.req. The substitutions file that can be loaded at boot time or flattened by msi into a database file.
To use it, one needs values for: the IP address of the instrument; the desired IOC PV prefix, P; the desired IOC PV name, DAU; and the handle that will be given to the driver for this instrument, HANDLE. The help can be seen by running mw100_probe with no arguments.
The resultant substitutions file will have entries for all the hardware channels, as well as all the constant channels and 60 (out of 300) of both the calculation and communication channels. In the future, an option will be added to changing the number of communication and calculation channels included.
Database Loading
The simplest way to load databases associated with a populated MW100 is by using the autogenerated substitutions file from mw100_probe.
This substitutions file references the database files using a relative path off of the YOKOGAWA_DAS variable, which needs to be set to the top of this module's installed directory. The synApps distribution does this automatically, but it can be done by hand by adding to the startup script (such as st.cmd) before loading the substitutions file a line like this:
epicsEnvSet("YOKOGAWA_DAS", "/my/path/to/YOKOGAWA_DAS")
To load the substitutions file, in the startup script, use
dbLoadTemplate("auto_mw100.substitutions")
MEDM display files
not finished
Records
There are currently 7 records supported for various purposes: ai, ao, bi, bo, mbbi, mbbo, and stringin. Record commands are also provided to determine the record function, and for record commands that can refer to multiple items or locations, addressing is used; a few commands also need sub-addressing.
DTYP format
When using the supported records with the commands, DTYP needs to be set to "Yokogawa MW100".
INP and OUT format
For each MW100, the handle provided to the driver is used with record device support. The general format of the INP or OUT field is one of the following.
- “@handle command”
- “@handle command:address”
- “@handle command:address.sub_address”
Interrupts
The input records will let you use interrupt scan mode (I/O Intr), and there are several interrupts used. The first four interrupts can be indirectly invoked after causing a read with their TRIG commands, although only the first three are necessary, as an information read is typically called when the status read notices a mode change into measurements mode.
- Input - This interrupt is called after reading all the input
channels, input modules and calculation addresses. - Output - This interrupt is called after reading all the output channels, output modules, communication addresses, and constant addresses.
- Status - This interrupt is called after reading the operational statuses of the MW100.
- Information - This interrupt is called after reading the MW100 and channel information that can’t be changed during measurement mode.
- Error - This interrupt is called after the error state of the MW100 occurs.
Addresses
The type of address needed depends on the record, but here are all the options. The format of the addresses comes directly from the MW100, and this is how they are used internally.
- Module addresses: 0-5
- Hardware channel addresses: 001-060 Each module (of the six possible modules) can use at most ten hardware addresses. If module 0 has ten channels, it uses addresses 001-010, etc.
- Calculation channel addresses: A001-A300
- Communication channel addresses: C001-C300
- Constant channel addresses: K01-K60
Commands
MODULE_STRING - Shows the module identification string for a location, or "empty" if one doesn't exist. Linked to information interrupt.
- stringin record: - Uses module address.
MODULE_PRESENCE - Shows whether a module is at a location. Linked to information interrupt.
- bi record: - Uses module address.
- 0 - Not present
- 1 - Present
MODULE_MODEL - Shows the module model number, with values being 110, 112, 114, 115, 120, or 125. Linked to information interrupt.
- longin record: - Uses module address.
MODULE_CODE - Shows the 3 character module code. Linked to information interrupt.
- stringin record: Uses module address.
MODULE_SPEED - Shows the module speed. Linked to information interrupt.
- mbbi record: Uses module address.
- 0 - Low
- 1 - Medium
- 2 - High
MODULE_NUMBER - Shows the number of module channels. Linked to information interrupt.
- longin record: Uses module address.
VAL - Send or read a numeric value for a channel. Input records are linked to either the input interrupt (input channels) or the output interrupt (output channels).
- This command is associated with several record types.
- bi record: Uses hardware addresses for binary digital input and output modules.
- bo record: Uses hardware addresses for binary digital output modules.
- longin record: Uses hardware addresses for binary integer input modules.
- ai record: Uses hardware addresses for analog input and output modules, as well as calculation, communication, and contant addresses.
- ao record: Uses hardware addresses for analog output modules, as well as calculation, communication, and contant addresses.
VAL_STATUS - Shows any special status for a value read from a channel. Records are linked to either the input interrupt (input channels) or the output interrupt (output channels).
- mbbi record: Uses any hardware or calculation addresses.
- 0 - Normal
- 1 - Overrange
- 2 - Underrange
- 3 - Measurement Skip/Computation Off
- 4 - Error
- 5 - Value Uncertain
ALARMS - Shows the alarms set for an input channel. Records are linked to either the input interrupt (input channels) or the output interrupt (output channels).
- mbbi record: Uses any hardware or calculation addresses. Each bit of the 4-bit value corresponds to the status of an alarm, as multiple alarms can occur simultaneously; bit 0 is defined as the least significant bit.
- bit 0 - Alarm 1
- bit 1 - Alarm 2
- bit 2 - Alarm 3
- bit 3 - Alarm 4
- The bit value is defined as the following.
- value 0 - Alarm off
- value 1 - Alarm on
ALARM - Shows the status for a particular alarm for an input channel. Records are linked to either the input interrupt (input modules) or the output interrupt (output modules).
- mbbi record: Uses any hardware or calculation addresses, with sub-address of 1-4. The value definitions follow, although the possible values for a record are actually determined by the module and the channel mode.
- 0 - No Alarm
- 1 - High Limit
- 2 - Low Limit
- 3 - Differential High Limit
- 4 - Differential Low Limit
- 5 - Rate-of-Change High Limit
- 6 - Rate-of-Change Low Limit
- 7 - Delay High Limit
- 8 - Delay Low Limit
ALARM_FLAG - Shows if an alarm for any channel is set. Linked to input interrupt, as it is assumed to be set more often than the output interrupt.
- bi record: No address used.
ALARM_ACK - Tells MW100 to acknowledge alarms. This record just needs to be PROC'd to work.
- bo record: No address used.
CH_STATUS - Shows the configuration for a channel. Linked to information interrupt.
- mbbi record: Uses any hardware or calculation addresses.
- 0 - Skip
- 1 - Normal
- 2 - Differential Input
CH_MODE - Shows the operational mode for a channel, which is different each type of module (if it exists). Linked to information interrupt.
-
mbbi record: Uses hardware addresses for supported modules.
-
Series 120 module (DAC)
- 0 - Skip
- 1 - Transmission
- 2 - Communication
-
Series 125 module (relay)
- 0 - Skip
- 1 - Alarm
- 2 - Communication
- 3 - Media
- 4 - Failure
- 5 - Error
-
UNIT - Shows the unit for a channel. Linked to information interrupt.
- stringin record: Uses any hardware or calculation addresses.
EXPR - Shows the expression used for a calculation channel. Linked to information interrupt.
- stringin record: Uses any calculation addresses.
IP_ADDR - Shows the IP address for the MW100. Linked to information interrupt.
- stringin record: No address used.
SETTINGS_MODE - Shows whether the MW100 is in settings mode. Linked to status interrupt.
- bi record: No address used.
- 0 - False
- 1 - True
MEASURE_MODE - Shows whether the MW100 is in measurement mode. Linked to status interrupt. This command is somewhat redundant to SETTINGS_MODE as they seem to always be the opposite of each other, but they come from different bits being set, so not sure.
- bi record: No address used.
- 0 - False
- 1 - True
OPMODE - Set the operational mode of the MW100.
- bo record: No address used.
- 0 - Measurement
- 1 - Settings
COMPUTE_MODE - Shows whether the MW100 has computations running. Linked to status interrupt. This can only be true when MEASURE_MODE is true.
- bi record: No address used.
- 0 - False
- 1 - True
COMPUTE_CMD - Send a command regarding the computational mode of the MW100.
- mbbo record: No address used.
- 0 - Start
- 1 - Stop
- 2 - Reset
- 3 - Clear
INP_TRIG - Trigger reading the input records for the MW100, which will then trigger the input interrupt. This record just needs to be PROC'd to work; typically the SCAN field is set to a time interval.
- bo record: No address used.
OUT_TRIG - Trigger reading the output records for the MW100, which will then trigger the input interrupt. This record just needs to be PROC'd to work; typically the SCAN field is set to a time interval.
- bo record: No address used.
STAT_TRIG - Trigger reading the MW100 status, which will then trigger the status interrupt; if an operational mode change to measurements is seen, it will cause a information read which will then trigger the information interrupt. This record just needs to be PROC'd to work; typically the SCAN field is set to a time interval.
- bo record: No address used.
INFO_TRIG - Trigger reading the information for channels and the MW100 that can't be changed during measurement mode. This command doesn't really need to be used if the STAT_TRIG command is called periodically. This record just needs to be PROC'd to work; typically the SCAN field is set to a time interval.
- bo record: No address used.
ERROR_FLAG - Shows if an error has happened. Linked to error interrupt.
- bi record: No address used.
ERROR - Retrieve one of the three error strings used to return vendor-supplied error messages (broken to 40 character lengths). Linked to error interrupt.
- stringin record: Uses an address of 1-3.
ERROR_CLEAR - Clears the MW100 error. This record just needs to be PROC'd to work.
- bo record: No address used.